Автоматические выключатели открытого исполнения SENTRON 3WL / Автоматические выключатели/ Разъединители нагрузки открытого типа SENTRON 3WL до 6300А
3WL1232-5..71-....
Fixed-mounted circuit breaker 4-pole, Size 2, IEC In=3200 A to 690 V, 50/60 Hz AC Icu=130 kA at 500 V Rear vertical connection
3WL1232-5..72-....
Fixed-mounted circuit breaker 4-pole, Size 2, IEC In=3200 A to 690 V, 50/60 Hz AC Icu=130 kA at 500 V Rear horizontal connection
3WL1232-5..76-....
Draw-out circuit breaker with slide-in module frame 4-pole, Size 2, IEC In=3200 A to 690 V, 50/60 Hz AC Icu=130 kA at 500 V Rear horizontal connection
3WL1232-5..77-....
Draw-out circuit breaker with slide-in module frame 4-pole, Size 2, IEC In=3200 A to 690 V, 50/60 Hz AC Icu=130 kA at 500 V Rear vertical connection
3WL1240-2..71-....
Fixed-mounted circuit breaker 4-pole, Size 2, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=66 kA at 500 V Rear vertical connection
3WL1240-2..77-....
Draw-out circuit breaker with slide-in module frame 4-pole, Size 2, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=66 kA at 500 V Rear vertical connection
3WL1240-2A.71-....
Fixed-mounted non-automatic air circuit switches 4-pole, Size 2, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=66 kA at 500 V Rear vertical connection
3WL1240-2A.77-....
Withdrawable non-automatic air circuit breaker with slide-in module frame 4-pole, Size 2, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=66 kA at 500 V Rear vertical connection
3WL1240-3..71-....
Fixed-mounted circuit breaker 4-pole, Size 2, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=80 kA at 500 V Rear vertical connection
3WL1240-3..77-....
Draw-out circuit breaker with slide-in module frame 4-pole, Size 2, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=85 kA at 500 V Rear vertical connection
3WL1240-3A.71-....
Fixed-mounted non-automatic air circuit switches 4-pole, Size 2, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=85 kA at 500 V Rear vertical connection
3WL1240-3A.77-....
Withdrawable non-automatic air circuit breaker with slide-in module frame 4-pole, Size 2, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=85 kA at 500 V Rear vertical connection
3WL1240-4..71-....
Fixed-mounted circuit breaker 4-pole, Size 2, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear vertical connection
3WL1240-4..77-....
Draw-out circuit breaker with slide-in module frame 4-pole, Size 2, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear vertical connection
3WL1240-4A.71-....
Fixed-mounted non-automatic air circuit switches 4-pole, Size 2, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear vertical connection
3WL1240-4A.77-....
Withdrawable non-automatic air circuit breaker with slide-in module frame 4-pole, Size 2, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear vertical connection
3WL1340-4..71-....
Fixed-mounted circuit breaker 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear vertical connection
3WL1340-4..72-....
Fixed-mounted circuit breaker 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear horizontal connection
3WL1340-4..73-....
Fixed-mounted circuit breaker 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Front connection top/bottom Single hole
3WL1340-4..74-....
Fixed-mounted circuit breaker 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Front connection top/bottom double hole
3WL1340-4..75-....
Draw-out circuit breaker Without guide frame 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear horizontal connection
3WL1340-4..76-....
Draw-out circuit breaker with slide-in module frame 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear horizontal connection
3WL1340-4..77-....
Draw-out circuit breaker with slide-in module frame 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear vertical connection
3WL1340-4..78-....
Draw-out circuit breaker with slide-in module frame 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V with connecting flange
3WL1340-4A.71-....
Fixed-mounted non-automatic air circuit switches 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear vertical connection
3WL1340-4A.72-....
Fixed-mounted non-automatic air circuit switches 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear horizontal connection
3WL1340-4A.73-....
Fixed-mounted non-automatic air circuit switches 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Front connection top/bottom Single hole
3WL1340-4A.74-....
Fixed-mounted non-automatic air circuit switches 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Front connection top/bottom double hole
3WL1340-4A.75-....
Withdrawable non-automatic air circuit breaker Without guide frame 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear horizontal connection
3WL1340-4A.76-....
Withdrawable non-automatic air circuit breaker with slide-in module frame 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear horizontal connection
3WL1340-4A.77-....
Withdrawable non-automatic air circuit breaker with slide-in module frame 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear vertical connection
3WL1340-4A.78-....
Withdrawable non-automatic air circuit breaker with slide-in module frame 4-pole, Size 3, IEC In=4000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V with connecting flange
3WL1340-5..71-....
Fixed-mounted circuit breaker 4-pole, Size 3, IEC In=4000 A up to 1150 V, 50/60 Hz AC Icu=130 kA at 500 V Rear vertical connection
3WL1340-5..72-....
Fixed-mounted circuit breaker 4-pole, Size 3, IEC In=4000 A up to 1150 V, 50/60 Hz AC Icu=130 kA at 500 V Rear horizontal connection
3WL1340-5..75-....
Draw-out circuit breaker Without guide frame 4-pole, Size 3, IEC In=4000 A up to 1150 V, 50/60 Hz AC Icu=130 kA at 500 V Rear horizontal connection
3WL1340-5..76-....
Draw-out circuit breaker with slide-in module frame 4-pole, Size 3, IEC In=4000 A up to 1150 V, 50/60 Hz AC Icu=130 kA at 500 V Rear horizontal connection
3WL1340-5..77-....
Draw-out circuit breaker with slide-in module frame 4-pole, Size 3, IEC In=4000 A up to 1150 V, 50/60 Hz AC Icu=130 kA at 500 V Rear vertical connection
3WL1340-5A.71-....
Fixed-mounted non-automatic air circuit switches 4-pole, Size 3, IEC In=4000 A up to 1150 V, 50/60 Hz AC Icu=130 kA at 500 V Rear vertical connection
3WL1340-5A.72-....
Fixed-mounted non-automatic air circuit switches 4-pole, Size 3, IEC In=4000 A up to 1150 V, 50/60 Hz AC Icu=130 kA at 500 V Rear horizontal connection
3WL1340-5A.75-....
Withdrawable non-automatic air circuit breaker Without guide frame 4-pole, Size 3, IEC In=4000 A up to 1150 V, 50/60 Hz AC Icu=130 kA at 500 V Rear horizontal connection
3WL1340-5A.76-....
Withdrawable non-automatic air circuit breaker with slide-in module frame 4-pole, Size 3, IEC In=4000 A up to 1150 V, 50/60 Hz AC Icu=130 kA at 500 V Rear horizontal connection
3WL1340-5A.77-....
Withdrawable non-automatic air circuit breaker with slide-in module frame 4-pole, Size 3, IEC In=4000 A up to 1150 V, 50/60 Hz AC Icu=130 kA at 500 V Rear vertical connection
3WL1350-4..71-....
Fixed-mounted circuit breaker 4-pole, Size 3, IEC In=5000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear vertical connection
3WL1350-4..72-....
Fixed-mounted circuit breaker 4-pole, Size 3, IEC In=5000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear horizontal connection
3WL1350-4..75-....
Draw-out circuit breaker Without guide frame 4-pole, Size 3, IEC In=5000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear horizontal connection
3WL1350-4..76-....
Draw-out circuit breaker with slide-in module frame 4-pole, Size 3, IEC In=5000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear horizontal connection
3WL1350-4..77-....
Draw-out circuit breaker with slide-in module frame 4-pole, Size 3, IEC In=5000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear vertical connection
3WL1350-4A.71-....
Fixed-mounted non-automatic air circuit switches 4-pole, Size 3, IEC In=5000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear vertical connection
3WL1350-4A.72-....
Fixed-mounted non-automatic air circuit switches 4-pole, Size 3, IEC In=5000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear horizontal connection
3WL1350-4A.75-....
Withdrawable non-automatic air circuit breaker Without guide frame 4-pole, Size 3, IEC In=5000 A up to 690 V, 50/60 Hz AC Icu=100 kA at 500 V Rear horizontal connection